Sensalert ASI

SensAlert ASI is for toxic & combustible gas detection and oxygen monitoring. It uses intrinsically safe or explosion proof installation configurations with options for remote sensors and gassing, duct mount, and sample-draw maximize application versatility. It also has configurations for remote sensors and gassing, duct mount, and sample-draw maximize application versatility. The sensor head accepts all Plus Series sensor technologies – infrared, catalytic bead, and electro-chemical.

Notify me on updates of this product 

Availability: Commercially Available

+1 800 738 7086
16333 Bay Vista Drive
Clearwater, FL 33760
USA
www.sensidyne.com
Manufacturer
Sensidyne LLP
Product Name
Sensalert ASI
Detection Category
Chemical
Detection Principle
Molecular Spectroscopy; Sensors;
Detection Method
Infrared (IR) Spectroscopy; Catalytic Bead Sensor; Electrochemical Detection ;
Application
Gas Analysis;
Equipment Type
Sensor
Product Synopsis
SensAlert ASI is for toxic & combustible gas detection and oxygen monitoring. It uses intrinsically safe or explosion proof installation configurations with options for remote sensors and gassing, duct mount, and sample-draw maximize application versatility. It also has configurations for remote sensors and gassing, duct mount, and sample-draw maximize application versatility. The sensor head accepts all Plus Series sensor technologies – infrared, catalytic bead, and electro-chemical.
Availability
Commercially Available
Technology Readiness Level (TRL)
9
User Feedback Sources
Indifferent/No user feedback
Dimensions
5.3 x 9.25 x 3.3 in (135 x 235 x 84 mm)
Weight
<5 lbs.; 1.9 lbs (.86 kg)
Power Requirements
AC/DC Line Power; 15-30 VDC
Transportability
Handheld
Ruggedness
None; intrinsically safe
Operating Conditions
-40 to 70°C( -40 to 158°F) instrument, -20 to 50°C (-4 to 122°F) sensor 0-90% RH, non-condensing
Consumables
<$1,000/year; Calibration gases, zero calibration gas, Tygon tubing
Calibration Schedule
Yes. A Sensor Calibration & Exchange Program with the manufacturer schedules delivery of factory calibrated sensors
Suggested Routine Maintenance
Minimal
Data Analysis Support Equipment
Universal gas transmitter, Wire XP transmitter, rainshield, regulator, PVC carrying case, humidification kit, calibration cup, teflon tubing
Communications Interface
An optional communications board can be installed for RS-485 with Modbus, or HART protocol.
Shelf Life
<5 years; Sensor shelf life – 6 months to 2 years from shipping date, depending on the sensor
Unit Cost
$1,525.00
Maintenance Cost
Cost of sensors $295 to $765, depending on gas measured
Other Chemical Targets
Toxic & combustible gas detection and oxygen monitoring
Sample Introduction
Vapor/Gas
Sensitivity/Detection Limits
ppm; %
Known Interferents/Inhibitors
Avoid sudden changes in pressure, lack of exposure to ambient air, and exposure to high concentrations of toxic gases
Start Up Time (From Cold Start To Sample Ready)
Sensor stabilization up to 2 hours, but may be used immediately
Response Time (Sample Application To Output)
<1 minute; < 15 seconds, successive exposures – O2 < 60 seconds, successive exposures – CH3OH
Alarm Capability
Yes, when equipped
Software Control
Plug and play available
Training Required
<1 week training
Manuals Available
Yes
Warranties
2 yr, IR sensors could be warranted for 5-7 yrs.
Please enter contact info.
Email Address: 
Company: 
Name: 
Title: