Trigard
The TRIGARD Gas Monitoring System is an area monitor that detects chlorine, sulfur dioxide and other toxic and combustible gases. The adjustable-range unit also detects oxygen deficiency and enrichment. AC or DC powered, the system features a LCD screen and push-button calibration. The unit offers multiple sensor mounting options. The sensor disconnect-underpower feature allows all sensors to be replaced in hazardous areas without area declassification, while interchangeable smart sensors are pre-calibrated for installation right out of the box.
Availability: Commercially available
+1 800 672 2222
1000 Cranberry Woods Drive
Cranberry Township, PA 16066
USA
|
|
www.msasafety.com
| Manufacturer |
| Mine Safety Appliances Company (MSA) |
| Product Name |
| Trigard |
| Detection Category |
| Chemical |
| Detection Principle |
| Sensors; |
| Detection Method |
| Catalytic Bead Sensor; |
| Application |
| Gas Analysis; |
| Equipment Type |
| Instrument |
| Product Synopsis |
| The TRIGARD Gas Monitoring System is an area monitor that detects chlorine, sulfur dioxide and other toxic and combustible gases. The adjustable-range unit also detects oxygen deficiency and enrichment. AC or DC powered, the system features a LCD screen and push-button calibration. The unit offers multiple sensor mounting options. The sensor disconnect-underpower feature allows all sensors to be replaced in hazardous areas without area declassification, while interchangeable smart sensors are pre-calibrated for installation right out of the box. |
| Availability |
| Commercially available |
| Technology Readiness Level (TRL) |
| 9 |
| User Feedback Sources |
| Indifferent/No user feedback |
| Dimensions |
| 6.89 x 9.84 x 5.87 in (17.5 x 25 x 15 cm) |
| Weight |
| <5 lbs. |
| Power Requirements |
| AC/DC Line Power; 12-30 VDC (standard), 85-256 VAC (optional) |
| Noise Produced |
| 95 Db |
| Transportability |
| Pocket Size |
| Operating Conditions |
| 0 to 30°C (32 to 86°F) |
| Consumables |
| None |
| Communications Interface |
| 1 sensor: 4-20 mA output, 3-wire or ModBus-RTU 2 or 3 sensors: ModBus-RTU only |
| Expected Operational Life |
| 10 years |
| Shelf Life |
| <5 years; Dependent on sensor, typically > 3 years |
| Unit Cost |
| $2,500 to $5,000 |
| Other Chemical Targets |
| Chlorine, sulfur dioxide, other toxic and combustible gases |
| Sample Introduction |
| Vapor/Gas |
| Start Up Time (From Cold Start To Sample Ready) |
| Seconds |
| Response Time (Sample Application To Output) |
| Continuous (<30 seconds) |
| Total Run Time |
| Continuous |
| Alarm Capability |
| Audible and visual |
| Software Control |
| On-board |
| Training Required |
| <1 week training |
| Training Available |
| Yes |
| Manuals Available |
| Yes |
| Warranties |
| 18 months from shipping or 1 year after installation whichever is first |
| IATA Shipping Restrictions |
| Not Specified |