Remediater (Detector Head)

The Delphian Remediater (Fixed Point Infrared) sensor is a smart infrared hydrocarbon gas detector. Designed for natural gas or methane detection. The Remediater measures percent by volume of combustible gases. An infrared beam is directed to a detector. The detector is a percent volume detector, similar to the Determinator, sold by the same company. Air is pulled into the sample cell. If the hydrocarbon of interest is above 5% LEL, then the detector will detect a drop in total emission energy.

Notify me on updates of this product 

Availability: Commercially Available

contact@delphian.com
1-800-288-3647
220 Pegasus Ave
Northvale, NJ 07647-1904
www.delphian.com/index.htm
Manufacturer
Delphian Corporation
Product Name
Remediater (Detector Head)
Detection Category
Chemical
Detection Principle
Molecular Spectroscopy;
Detection Method
Infrared (IR) Spectroscopy ;
Application
Gas Analysis;
Equipment Type
Sensor
Product Synopsis
The Delphian Remediater (Fixed Point Infrared) sensor is a smart infrared hydrocarbon gas detector. Designed for natural gas or methane detection. The Remediater measures percent by volume of combustible gases. An infrared beam is directed to a detector. The detector is a percent volume detector, similar to the Determinator, sold by the same company. Air is pulled into the sample cell. If the hydrocarbon of interest is above 5% LEL, then the detector will detect a drop in total emission energy.
Availability
Commercially Available
Technology Readiness Level (TRL)
9
User Feedback Sources
Indifferent/No user feedback
Dimensions
13 x 6 in (331 x 153 mm)
Weight
<30 lbs.; 6 lbs (2.7 kg)
Power Requirements
AC/DC Line Power; 24 V DC
Transportability
Pocket Size
Operating Conditions
-30 to 70°C 0 to 99% RH, non-condensing
Calibration Schedule
Span calibration is not required and zero point adjustment required infrequently
Available Accessories
$1,625 complete system
Data Analysis Support Equipment
Uses aluminum and stainless steel sensors, splash/dust guard, lightning arrestor, SLAM (local alarm relay module), reclamation adaptor
Communications Interface
4-20 mA output and Standard RS 422/485 output is available. Can interface with most digital protocols using a separate module.
Shelf Life
>5 years
Unit Cost
$868.00
Other Chemical Targets
A natural gas or methane detector
Sample Introduction
Vapor/Gas
Sensitivity/Detection Limits
%; %LEL
Known Interferents/Inhibitors
Only one gas may be measured at a time, if multiple gases are present it may present errors with reading
Start Up Time (From Cold Start To Sample Ready)
Depends on temperature. If temperatures are extreme, it could take an hour. At normal temperatures, ~ 1 minute
Response Time (Sample Application To Output)
Continuous (<30 seconds); <10 seconds
Alarm Capability
Yes
Software Control
Yes, comes with conduit box, interface and processor modules
Training Required
<1 week training
Manuals Available
Yes
Warranties
2 yr
Please enter contact info.